Task: | Program |
---|---|
Structure: | Closed-Loop |
Mathematical Model: | Linear |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Name
|
16-point Contact Output Unit with Terminal Block
|
|
|
|
|||
Model
|
CJ1W-OC211
|
|
|
|
|||
Max. Switching Capacity
|
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit)
|
|
|
|
|||
Min. Switching Capacity
|
1 mA 5 VDC
|
|
|
|
|||
Relays
|
NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced.
|
|
|
|
|||
Service Life of Relay
|
Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 operations (250 VAC, cosφ = 0.4, inductive load) Mechanical:
20,000,000 operations Service life will vary depending on the connected load. |
|
|
|
|||
ON Response Time
|
15 ms max
|
|
|
|
|||
OFF Response Time
|
15 ms max
|
|
|
|
|||
Number of Circuits
|
16 points/common, 1 circuit
|
|
|
|
|||
Insulation Resistance
|
20 MΩ between external terminals and the GR terminal (500 VDC)
|
|
|
|
|||
Dielectric Strength
|
2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max
|
|
|
|
|||
Internal Current Consumption
|
110 mA 5 VDC max. 96 mA 24 VDC max. (6 mA × No. of ON points)
|
|
|
|
|||
Weight
|
170 g max
|
|
|
|